Step
What to check
Requirement
1. Hydraulic node
EZ solenoid valve, water meter, mesh filter, non-return valve — according to the diagram
mandatory
2. Service bypass
Parallel bypass with a manual valve sealed in the closed position
mandatory
3. RE distribution board
Correct cabinet installation, power supply from a distribution board with surge protection
mandatory
4. Flood probe
2–3 mm above the floor, at the lowest point, in the run-off path; in a drain grate — in its upper part
recommended
5. Acceptance tests
Leak simulation, EZ shut-off, reset — positive result
mandatory
6. Protocol
Signed commissioning and handover protocol (operating and maintenance manual)
mandatory